Three-phase induction motor testing
The
test rig performancehas been evaluated by testing a small size
three-phase induction motorwhose rated parameters are listed in
Table I. In the following the different tests performed with the three-phase induction motor are described in detail.
A. Measurement of the quasi-static torque characteristics
The
torque characteristicscan be easily determined by imposing to the DM speed control scheme a particular
reference speed ramp, while the MUT is supplied with the
rated voltage. A low value for the speed ramp acceleration is desired to impose a
quasi-static operating conditionfor the MUT, but the
ramp timebecomes high. At the same time, the ramp time should be limited to avoid an important increase of the MUT temperature during the test.
Power (W) |
1500 |
Voltage (V) |
400 |
Current (A) |
3.8 |
Frequency (Hz) |
50 |
Number of poles |
4 |
Speed (rpm) |
1405 |
Torque (Nm) |
10.2 |
Starting torque (Nm) |
19.8 |
Peak torque (Nm) |
26.4 |
Table 1: Rated data of the tested three-phase induction motor Therefore, the
length of the speed rampshould be chosen as a reasonable
compromise between the quasi-static condition and the increase of the MUT temperatureduring the test. For this reason, the authors adopted a
speed profilecontaining two different sections having two different accelerations, as shown in
Fig. 6. In particular, a
faster speed ramphas been used from the zero up to a speed value that corresponds to the pull-out torque, while a
slower ramphas been defined
Three-phase induction motor testing
The
test rig performance has been evaluated by testing a small size
three-phase induction motor whose rated parameters are listed in
Table I. In the following the different tests performed with the three-phase induction motor are described in detail.
A. Measurement of the quasi-static torque characteristics
The
torque characteristics can be easily determined by imposing to the DM speed control scheme a particular
reference speed ramp, while the MUT is supplied with the
rated voltage. A low value for the speed ramp acceleration is desired to impose a
quasi-static operating condition for the MUT, but the
ramp time becomes high. At the same time, the ramp time should be limited to avoid an important increase of the MUT temperature during the test.
Power (W) | 1500 |
Voltage (V) | 400 |
Current (A) | 3.8 |
Frequency (Hz) | 50 |
Number of poles | 4 |
Speed (rpm) | 1405 |
Torque (Nm) | 10.2 |
Starting torque (Nm) | 19.8 |
Peak torque (Nm) | 26.4 |
Table 1: Rated data of the tested three-phase induction motor
Therefore, the
length of the speed ramp should be chosen as a reasonable
compromise between the quasi-static condition and the increase of the MUT temperature during the test. For this reason, the authors adopted a
speed profile containing two different sections having two different accelerations, as shown in
Fig. 6. In particular, a
faster speed ramp has been used from the zero up to a speed value that corresponds to the pull-out torque, while a
slower ramp has been defined to reach the synchronous speed. In this way, a
better quasi-static condition can be obtained in the stable part of the torque vs. speed characteristic.
It is very important to avoid
speed oscillations during the test; this is possible only if the DM
speed control dynamic performance is high, as explained in the previous section.
With reference to
Fig.6, it should be also noted that the MUT is supplied at the time instant t0 and it is blocked at zero speed by the DM during the time interval Δt1. This time interval allows
measuring the ‘real’ starting torque of the machine when the transient phenomena following the supply switch turn-on are extinct.
The
torque versus speed and the torque versus current characteristics for three different values of the supply voltage are reported in
Fig.7 and Fig.8, respectively.
The
three starting tests with different supply voltage have been performed in rapid sequence with the machine at the ambient temperature. From the characteristics reported in Fig.7 and Fig. 8 it is possible to see that the squared proportionality between the torque and the supply voltage is reasonably respected.
B. Locked rotor test
The locked rotor test is one of the standard tests required for the
induction motor equivalent circuit parameter determination. With the proposed test rig, this test can be easily performed imposing a
speed equal zero to the DM speed control. Since the motor under test is connected to the torque-meter the starting torque at reduced voltage (the locked rotor voltage) can be measured too.
C. No-load test at synchronous speed
This test allows to
determine the magnetizing current and the iron losses with an excellent accuracy because the mechanical and windage losses are compensated by the DM. The test is performed by imposing to the DM a
mechanical speed equal to the MUT synchronous speed; in this case the MUT slip will be zero. To get a true MUT zero slip, the
DM supply frequency must be equal to the supply frequency of the motor under test. This condition can be obtained
by linking the output frequency of the drive to the frequency of the main by means of a PLL.
Any other solution which cannot guarantee an isofrequency condition must not be used because a slip not perfectly equal to zero introduces losses in rotor with a wrong evaluation of the iron losses.
D. Efficiency test
The efficiency test is a
long duration test used for the determination of the
induction motor efficiency [4]. During this test, the DM is used as a brake for imposing the rated torque to the MUT. Thanks the regenerative drive used in the test bench, the
shaft power can be recovered in the grid and only the
total losses of the system must be provided. At the end of the thermal tests, the drive can be programmed to perform the
variable load test, applying the
load torque profile imposed by the standard [10]-[12]. The variable load test is required to
estimate the stray load losses.
At the end of the rated
load temperature tests, the
acceleration test can be quickly repeated in order to evaluate the
effect of the temperature on the electromechanical characteristics, with respect to the cold condition. For the considered three-phase induction motor the torque variation with the temperature is reported in
Fig. 9, for a stator winding temperature of around 25°C and 105 °C (measured at the end of the temperature test), respectively. The performed measurements prove
that both in cold and hot conditions the motor provides a starting torque higher than the value declared by the manufacturer (reported in Table I). In hot condition, the pull-out torque design value of the machine is confirmed by the measurements.
It has been also verified that on the
torque-speed plane, the working point measured during the rated load temperature test (10.2 Nm @ 1402 rpm) reasonably lays on the
torque vs. speed characteristic measured during the starting test in hot condition (10.2 Nm @ 1399 rpm); this results confirming that,
thanks to the proposed test rig, it is really possible to estimate quasi-static electromechanical characteristics of induction machines.
E. Test for the rotor time constant evaluation
The
rotor time constant is a key parameter for
rotor flux estimation in high performance induction motor vector control [13]. This test can be done using the same operating condition of the no-load test at synchronous speed. The
DM is speed controlled and imposes zero a slip to the MUT. While the motor under test is running in
synchronous condition and it is supplied with its
rated voltage, the
main switch is turned-off.
The
data acquisition system is used to store the
voltage at the terminal of the motor under test. This voltage will be equal to the supply voltage when the
main switch is in
“ON” position, while it will be equal to the stator Electro-Motive Force (EMF) produced by the rotor flux when the main switch is in the
“OFF” position. The
EMF amplitude will decay as first order system defined by the rotor time constant. The
envelope of the stator EMF waveforms allows
evaluating the rotor time constant with an excellent accuracy, because the rotor time constant is evaluated in an electromagnetic condition very close to the operative one. In fact, the time constant computed with this method is not affected by the rotor current skin effects, as happens when it is computed using the rotor parameter values coming from the locked rotor test.
For an accurate estimation of the rotor time constant, the authors used the
decay of the stator voltage vector magnitude computed as the square root of the stationary frame (alfa, and beta) stator induced voltage components An example of the data available after performing the rotor time constant evaluation test is reported in
Fig.10, where is well evident the decay of the stator EMF amplitude when the main switch is turned off. For the tested motor a rotor time constant equal to 114 ms has been estimated.
F. Standard no-load test
The classical no-load test is again one of the standard tests used for
determination of the induction motor equivalent circuit parameters. For this test, the proposed test rig is not necessary because during the test the motor has to be free to rotate without mechanical load connected to the motor shaft.
For performing this test the motor under test has to be just mechanically disconnected from the torque-meter and the DM shaft. The data acquisition system is still used synchronizing the time interval for the measurements with the supply voltage applied to the MUT.